Technical Aid

COLOUR CODE

 

Power cable up to and including 1,8/3kV
No. of cores Earth Core Phase
2 - Blue Brown    
2+E Green-Yellow Blue Brown    
3 - Brown Black Grey  
3+E Green-Yellow Brown Black Grey  
4 - Blue Brown Black Grey
4+E Green-Yellow Blue Brown Black Grey
5 & above Black or White insulation, printed numbered core
HV power cable higher than 1,8/3kV
No. of cores Phase
3 Blue Brown Black

 

Signal / Instrumentation
Conductor Phase
Pair Blue Black  
Traid Blue Black Red

 

 

AWG to Metric conversion table

 

Below are some of the some of the popular strandings, nevertheless there are many other combinations exist. Value for resistance are given but please be inform that this is only as guidance.

AWG Cross Section (mm2) Stranding (mm) Resistance (Ohm/km)
38 0,008 1x0,10 2125
38 0,009 7x0,04 1930
36 0,013 1x0,12 1360
36 0,014 7x0,05 1217
34 0,02 1x0,16 856
34 0,022 7x0,06 777
32 0,032 1x0,20 538
32 0,034 7x0,08 538
32 0,035 19x0,05 446
30 0,051 1x0,25 338
30 0,057 7x0,10 338
30 0,059 19x0,06 286
28 0,08 1x0,32 213
28 0,089 7x0,12 213
28 0,09 19x0,08 186
26 0,128 1x0,40 134
26 0,141 7x0,16 122
26 0,155 19x0,10 113
24 0,205 1x0,51 84
24 0,227 7x0,20 76
24 0,241 19x0,12 69
22 0,324 1x0,64 53
22 0,355 7x0,25 48
22 0,382 19x0,16 45
20 0,519 1x0,81 33
20 0,563 7x0,32 30,4
20 0,616 19x0,20 28,3
18 0,785 16x0,25 21,2
18 0,823 1x1,02 20,9
AWG Cross Section (mm2) Stranding (mm) Resistance (Ohm/km)
18 0,9 7x0,40 19,2
18 0,96 19x0,25 17,9
16 1,3 1x1,29 13,2
16 1,23 19x0,28 14
14 2,08 1x1,62 8,28
14 1,94 19x0,36 8,86
12 3,31 1x2,05 5,2
12 3,08 19x0,45 5,58
10 5,26 1x2,58 3,28
10 5,26 19x0,6 3,28
8 8,38 1x3,26 2,06
8 8,35 19x0,75 2,06
6 13,29 1x4,11 1,59
6 13,29 19x0,96 1,59
4 21,15 1x5,18 0,815
4 21,14 19x1,19 0,815
2 33,63 1x6,54 0,513
2 33,61 19x1,50 0,513
1 42,41 1x7,34 0,424
1 42,38 19x1,68 0,424
1/0 53,4 19x1,89 0,253
2/0 67,4 19x2,17 0,291
4/0 107 19x2,68 0,182
250 MCM 127 37x2,09 0,139
300 MCM 152 37x2,29 0,119
350 MCM 177 37x2,47 0,102
400 MCM 202 37x2,64 0,091
500 MCM 253 37x2,95 0,072

 

 

Stranding chart

 

Cross Section (mm2) Class 2 Class 5
No. of wires Resistance (Ohm/km) Diameter, mm No. of wires Resistance (Ohm/km) Diameter (mm)
1,5 7 12,1 1,5 25 13,30 1,5
2,5 7 7,41 1,8 42 7,98 1,9
4 7 4,61 2,3 48 4,95 2,5
6 7 3,08 2,9 72 3,30 3,0
10 7 1,83 3,8 70 1,91 4,0
16 7 1,15 4,7 111 1,21 5,0
25 7 0,727 5,8 172 0,78 6,2
35 7 0,524 6,9 242 0,554 7,3
50 12 0,387 8,0 348 0,386 8,7
70 19 0,268 9,5 312 0,272 10,6
95 19 0,193 11,3 420 0,206 12,2
120 19 0,153 12,9 532 0,161 14,0
150 37 0,124 14,3 679 0,129 15,4
185 37 0,0991 15,7 819 0,106 16,9
240 60 0,0754 17,9 1099 0,0801 19,8
300 60 0,0601 20,3 1386 0,0641 23,0
400 60 0,0470 23,0 1888 0,0486 27,0
500 61 0,0366 27,1 2384 0,0384 30,7
630 61 0,0283 30,9 3120 0,0287 34,5

 

 